Stoneworks access Floor Panels

Stoneworks Access Floor Panels

  Tate's STONEWORKS™ Panel

  Tate's STONEWORKS panels eliminate the need for finish lamination as the high-end architectural finish and the structural integrity of the panel is combined into a single integrated panel. STONEWORKS panels are engineered to meet Tate Standards per CISCA testing methods.

b9a15393ebef625deb42bb676cab578a.jpg

  System Characteristics

  Meets Tate Standards per CISCA testing methods

  Design loads of 1250 lbs with a safety factor of 1.44

  Non-combustible

  E-coated steel bottom sheet

  Beveled sides with edge banding

  System Performance

  Tate Standards to CISCA Testing Methods

  System Performance Criteria (Tested on Actual Understructure*)

System TypeSystem Weight (lbs/ft2)Static LoadsRolling LoadsImpact Loads
PanelUnderstructureDesign Loads1Minimum
Ultimate Loads
Safety Factor210 Passes10,000 Passes
STONEWORKS™ PanelHeavy-Duty Bolted Stringer15.5 lbs/ft21250 lbs1800 lbs1.441000 lbs800 lbs100 lbs

*All tests are performed using CISCA's Recommended Test Procedures for Access Floors with the exception of Design Load

1. System Design Load is based on permanent set ≤ 0.010” and is verified by loading panels in accordance with the CISCA concentrated load method but with panels installed on actual understructure instead of steel blocks. (Testing on blocks does not represent performance of an actual installation.) Ultimate, Rolling, and Impact Load tests are performed using CISCA Test Procedures.
2. Safety Factor is Ultimate Load divided by Design Load. 